2% Rabatt auf Online-Bestellungen
Details
cable with circuit integrity 30 min cable conform to Low Voltage directive cable with function maintainance 180 min flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free min. installation temperature -5 °C cable with VDE-certification
p/nr.Part nameAvailabilityPackagingEUR netto pre-metal per 1.000 m.
102101JE-H(ST)H BD E30 01X2X0.8 RD
on request
Aufmachung

Log in to see prices

New here? Register now
Preis
100427JE-H(St)H...Bd...E30 2X2X0.8 RD
in stock
AufmachungPreis
100428JE-H(St)H...Bd...E30 4X2X0.8 RD
in stock
AufmachungPreis
100429JE-H(St)H...Bd...E30 8X2X0.8 RD
in stock
AufmachungPreis
100430JE-H(St)H...Bd...E30 12X2X0.8 RD
in stock
AufmachungPreis
100431JE-H(St)H...Bd...E30 16X2X0.8 RD
on request
AufmachungPreis
100432JE-H(St)H...Bd...E30 20X2X0.8 RD
in stock
AufmachungPreis
100433JE-H(St)H...Bd...E30 32X2X0.8 RD
in stock
AufmachungPreis
100434JE-H(St)H...Bd...E30 40X2X0.8 RD
on request
AufmachungPreis
100435JE-H(St)H BD E30 52X2X0.8 RD
in stock
AufmachungPreis
Customs Tariff Number (code number) 85444991000000000
Conductor material copper, bare
Conductor construction Class 1 = solid
Insulation FRNC-compound HI1
Screen Foil
Drain wire yes
Sheathing material FRNC-compound HM2
Colour of outer sheath red
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
Fire-resistant FE 180
Circuit integrity E30
Permitted outer cable temperature, fixed, °C -30 - +70 °C
Bending radius, fixed installation 7.5 x Ø
Core identification colours acc. to VDE 0815
diameter conductor 0.8 mm
metal base Cu 100 EUR/100 kg
Unit of measurement metre

For signal transmission between electronic devices, in computer systems of process control units in fire hazard rooms with a high concentration of people or material assets and for installation of circuits with circuit integrity E30/E90 according to DIN 4102 part 12, with tested cable systems. For fixed installation in dry and damp areas on certified carrier systems. By the special sheath printing -Brandmeldekabel- this cable is particularly designed for the use in fire signalisation systems.

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metal regarding the daily market price.

Contact
Cable calculator