• Sprache wechseln DE
    |
    EN
  • Cart
CU/AL
0 0

NHXCH E30 03X150/70 RM OG

Art.-Nr. 011831

NHXCH E30 03X150/70 RM OG
  • Item list
  • Technical data
  • Application
  • Technical documents
Customs Tariff Number (code number)85446010000000000
StandardVDE 0266
Conductor materialcopper, bare
Conductor constructionclass 1, from 25 sqmm class 2
InsulationFRNC-compound HI1
Concentric conductorCu
Sheathing materialFRNC-compound HM1
Colour of outer sheathorange
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke densityDIN EN 61034/IEC 61034
Halogen-freeDIN EN 50267/IEC 60754
Fire-resistantFE 180
Circuit integrityE30
Maximum permitted conductor temperature, °C90 °C
Permitted outer cable temperature, fixed, °C-5 - +70 °C
Bending radius, fixed installation12 x DA
Nominal voltage Uo600 V
Nominal voltage U1000 V
Core identificationcolours acc. to HD 308; more than 5 cores: numbers
Core identificationcolours acc. to HD 308; more than 5 cores: numbers
Conductor shaperound
Conductor shape (Faber)RM
Number of cores3
Nominal cross section, sqmm150 mm²
Conductor resistance0.124 Ohm/km
Ampacity in air (30 °C)416 A
Cross-section of concentric conductor70
Bending radius, fixed installation629 mm
outer diameter approx.46.90 mm
Colour of outer sheathorange
Copper weight (GER)5100 kg/km
net weight7713 kg/km
VDEyes
GOST/EACyes
Nominal voltage0,6/1 kV
Sheathing materialFRNC-compound
Cable shaperound
Halogen-freeyes
Oil-resistantno
Colourorange
Conductor constructionclass 2 = stranded
InsulationFRNC-compound

For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 (180 min.= IEC 60331). Furthermore the cable passed the test of 30 min. circuit integrity according to DIN 4102 part 12 (E 30) for all so-called standard installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 800 °C is approximately four times higher than at 20 °C and the current carrying capacity is reduced respectively.

p/nr. Part name Availability Packaging EN: EUR netto pre-metal per 1.000
011831 NHXCH E30 03X150/70 RM OG on request
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact

 

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Deutschland

Phone +49 681 97 11-289
Fax +49 681 97 11-289