(N)HXH FE180/E90

Item list
Technical data
Application
Technical documents
Customs Tariff Number (code number) | 85444995000000000 |
Standard | VDE 0266 |
Conductor material | copper, bare |
Conductor construction | class 1, from 25 sqmm class 2 |
Insulation | FRNC-compound HI1 |
Sheathing material | FRNC-compound HM1 |
Colour of outer sheath | orange |
Flame-retardant | VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C) |
Smoke density | DIN EN 61034/IEC 61034 |
Halogen-free | DIN EN 50267/IEC 60754 |
Fire-resistant | VDE 0472-814/IEC 60331-11 (FE 180) |
Circuit integrity | E90 |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | -30 - +90 °C |
Permitted outer cable temperature, moved, °C | -5 °C |
Bending radius, fixed installation, multicore | 12 x Ø |
Conductor shape | round |
Colour of outer sheath | orange |
metal base Cu | 0 EUR/100 kg |
Unit of measurement | metre |
For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 (180 min., = IEC 60331), EN 50200 and EN 50362. Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so-called standard installation systems (ladder, tray and ceiling). A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.