cable with circuit integrity 90 min cable with function maintainance 180 min flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free max. permitted temperature at conductor 90 °C cable with VDE-certification cable with EAC-approval cable conform to Low Voltage directive

cable with circuit integrity 90 mincable with circuit integrity 90 min

cable with function maintainance 180 mincable with function maintainance 180 min

flame retardant acc. IEC 60332-3-24flame retardant acc. IEC 60332-3-24

cable with low smoke IEC 61034cable with low smoke IEC 61034

cable halogen-freecable halogen-free

max. permitted temperature at conductor 90 °Cmax. permitted temperature at conductor 90 °C

cable with VDE-certificationcable with VDE-certification

cable with EAC-approvalcable with EAC-approval

cable conform to Low Voltage directivecable conform to Low Voltage directive

  • Item list
  • Technical data
  • Application
  • Technical documents
Customs Tariff Number (code number)85446010000000000
StandardVDE 0266
Conductor materialcopper, bare
Conductor classclass 1, from 25 sqmm class 2
InsulationFRNC-compound HI1
Concentric conductorCu
Sheathing materialFRNC-compound HM1
Colour outer sheathorange
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke densityDIN EN 61034/IEC 61034
Halogen-freeDIN EN 50267/IEC 60754
Fire-resistantFE 180
Circuit integrityE90
Maximum permitted conductor temperature, °C90 °C
Permitted outer cable temperature, fixed, °C-5 - +70 °C
Bending radius, fixed installation12 x DA
Nominal voltage Uo600 V
Nominal voltage U1000 V
Core identificationcolours acc. to HD 308; more than 5 cores: numbers
Conductor shape (Faber)RM
Number of cores4
Nominal cross section, sqmm185 mm²
Conductor resistance0.0991 Ohm/km
Ampacity in air (30 °C)480 A
Cross-section of concentric conductor95
Bending radius, fixed installation804 mm
Outer diameter approx.67.5 mm
Colour of outer sheathorange
Copper weight (GER)8159 kg/km
weight10894 kg/km
VDEyes
GOST/EACyes
Nominal voltage0,6/1 kV
Cable shaperound
Sheathing materialFRNC-compound
Halogen-freeyes
Oil-resistantno
colourorange
Conductor classclass 2 = stranded
InsulationFRNC-compound

For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 (180 min. = IEC 331). Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so-called standard installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.

p/nr. Part name Availability Packaging EUR netto pre-metal per 1.000
011005 NHXCH E90 04X185/95 RM OR Stock
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-289
Fax +49 681 97 11-289