cable with circuit integrity 90 min cable with function maintainance 180 min flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free max. permitted temperature at conductor 90 °C cable with VDE-certification cable conform to Low Voltage directive
0136670400500
drum 500 m
Invalid input!
on request
Price
Price
Price
0136670401000
drum 1000 m
Invalid input!
on request
Price
Price
Price
0136670400000
cut length
Invalid input!
on request
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85444995900000000
Standard VDE 0266
Conductor material copper, bare
Conductor construction class 1, from 25 sqmm class 2
Insulation FRNC-compound HI1
Sheathing material FRNC-compound HM1
Colour of outer sheath orange
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
Fire-resistant VDE 0472-814/IEC 60331-11 (FE 180)
Circuit integrity E90
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -30 - +90 °C
Permitted outer cable temperature, moved, °C -5 °C
Bending radius, fixed installation, multicore 12 x Ø
Core identification colours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Conductor shape (Faber) RM
Number of cores 5
Nominal cross section, sqmm 35 mm²
Conductor resistance 0.524 Ohm/km
Ampacity in air (30 °C) 162 A
Bending radius, fixed installation 400 mm
outer diameter approx. 33.30 mm
Copper weight (GER) 1680
metal base Cu 0 EUR/100 kg
net weight per 1000 2462 kg
Unit of measurement metre
VDE yes
Nominal voltage 0,6/1 kV
Sheathing material FRNC-compound
Cable shape round
Halogen-free yes
Oil-resistant no
Colour orange
Conductor construction class 2 = stranded
Insulation FRNC-compound

For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in the ground and not for use in water. The cable has improved properties in case of fire and may be used in public buildings with high safety requirements. The cable is halogen-free, has a low smoke density and is fire-resistant according to VDE 0472 part 814 /IEC 60331-11 for 180 minutes. Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so-called standard installation systems (ladder, tray and ceiling). A special test certificate about the circuit integrity is issued by -The Civil Engineering Materials Testing Institute-. For calculation of electrical systems with circuit integrity has to be considered that electrical resistance of copper conductors at 1000 °C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.