Faber® EIB-bus cable burial 2X2X0.8 BK
Your p/nr.
on request
on request
Customs Tariff Number (code number) | 85444991000000000 |
Conductor material | copper, bare |
Conductor construction | Class 1 = solid |
Insulation | polyethylene |
Stranding unit | pair |
Stranding | Layers |
Screen | plastic coated aluminium foil + solid copper drain wire |
Sheathing material | polyethylene |
Colour of outer sheath | black |
UV-resistant | yes |
Permitted outer cable temperature, fixed, °C | -30 - +70 °C |
Permitted outer cable temperature, moved, °C | -5 - +50 °C |
Bending radius, fixed installation | 7.5 x Ø |
Insulation resistance | 100 MOhmxkm |
Number of cores | 4 |
Loop resistance | 73.2 Ohm/km |
outer diameter approx. | 8.00 mm |
Copper weight (GER) | 21 |
metal base Cu | 100 EUR/100 kg |
net weight per 1000 | 75 kg |
Unit of measurement | metre |
Conductor diameter, mm | 0.8 mm |
Direct burial | yes |
Sheathing material | polyethylene |
Cable shape | round |
Halogen-free | no |
Oil-resistant | no |
Colour | black |
Conductor construction | class 1 = solid |
Insulation | polyethylene |
Due to the increased test voltage and the special marking the cable is designed as bus cable in the EIB/KNX facility control system according to EN 50090. For the Instabus itself is used only the red/black pair (transmission of 24 V supply voltage plus data packages), the second pair (white/yellow) is redundant.The cable may be installed on or under plaster, in ducts and buried in the ground.