flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free screened cable cable suitable for direct burial max. permitted temperature at conductor 90 °C installation in free air without UV-protection (cable UV-resistant)
0371020400500
drum 500 m
Invalid input!
on request
Price
Price
Price
0371020401000
drum 1000 m
Invalid input!
on request
Price
Price
Price
0371020400000
cut length
Invalid input!
in stock
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85444995900000000
CPR-classification according to EN 50575 Dca
Conductor material copper, bare
Conductor construction Class 5 = flexible
Insulation XLPE
Screen aluminium foil + tinned copper braid
Screen coverage 75 %
Sheathing material FRNC-compound ST8
Colour of outer sheath black
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
UV-resistant yes
Ozone-resistant yes
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -40 - +90 °C
Permitted outer cable temperature, moved, °C -5 - +90 °C
Core identification colours acc. to VDE 0293 (HD308)
Number of cores 4
Nominal cross section, sqmm 16 mm²
Conductor resistance 1.21 Ohm/km
Ampacity in air (30 °C) 98 A
Ampacity in ground (20 °C) 112 A
outer diameter approx. 20.60 mm
Copper weight (GER) 789
metal base Cu 150 EUR/100 kg
net weight per 1000 628 kg
Unit of measurement metre
crane cables / hoist cables yes
Nominal voltage 0,6/1 kV
Sheathing material FRNC-compound
Cable shape round
Halogen-free yes
Oil-resistant no
Colour black
Conductor construction class 5 = fine stranded
Insulation XLPE

Halogen-free and flame-retardant cable connecting motors to inverse rectifiers under consideration of EMC-requirements. It may be used under medium mechanical stress for fixed installations and temporary movement. Suitable for indoor and outdoor installation as well as for direct ground burial.

All images shown here are for illustrations and product reference purposes only.

Contact