YSLYCY 600

Item list
Technical data
Application
Technical documents
Customs Tariff Number (code number) | 85446010000000000 |
CPR-classification according to EN 50575 | Eca |
Conductor material | copper, bare |
Conductor construction | Class 5 = flexible |
Insulation | PVC |
Material inner sheath | PVC |
Screen | tinned copper braid |
Screen coverage | 70 % |
Sheathing material | special PVC-compound |
Colour of outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 70 °C |
Permitted outer cable temperature, fixed, °C | -40 - +70 °C |
Permitted outer cable temperature, moved, °C | -5 - +70 °C |
Bending radius, fixed installation | 5 x Ø |
Bending radius, moving application | 10 x Ø |
Maximum tensile strength at the conductor | 15 N/mm² |
Colour of outer sheath | black |
metal base Cu | 150 EUR/100 kg |
Unit of measurement | metre |
Flexible power, process control and instrumentation cable for industry and machinery environment with specific EMC (electromagnetic compatibility) requirements. The cable is resistant to UV-irradiation, to most commonly used chemicals and to oil and grease. For indoor and outdoor application.
All images shown here are for illustrations and product reference purposes only.
Freight cost extra. Prices plus metal regarding the daily market price.