Customs Tariff Number (code number) 85444995900000000
Conductor material copper, bare
Conductor construction fine stranded
Insulation polyethylene
Stranding unit pair
Material inner sheath polyethylene
Screen tinned copper braid
Screen coverage 80 %
Sheathing material PVC
Flame-retardant EN 60332-1-2
Permitted outer cable temperature, fixed, °C -40 -+70 °C
Bending radius, fixed installation 10 x Ø
Insulation resistance 10000 MOhmxkm
Specific inductivity 0.75 mH/km
Nominal voltage U 150 V
Number of cores 2
Nominal cross section, sqmm 1.5 mm²
Conductor resistance 13.3 Ohm/km
outer diameter approx. 13.00 mm
Colour of outer sheath black
Copper weight (GER) 97.51
metal base Cu 150 EUR/100 kg
net weight per 1000 207 kg
Unit of measurement metre
Sheathing material PVC
Cable shape round
Halogen-free no
Oil-resistant no
Colour black
Conductor construction class 6 = extra finely stranded
Insulation polyethylene

Bus-cable for special application