3X50 + 3X25/3 0.6/1 kV BK
Your p/nr.
MOQ
MOQ: 1 km
Delivery time: approx. 30 weeks
MOQ
MOQ: 1 km
Delivery time: approx. 30 weeks
in stock
Customs Tariff Number (code number) | 85444995900000000 |
Standard | VDE 0250-814 (wih reference to) |
Conductor material | copper, bare |
Conductor construction | Class 5 = flexible |
Insulation | rubber (EPR) 3GI3 |
Arrangement of protective conductors | split in the outer interstices |
Material inner sheath | Gummi 5GM3 |
Torsion protection | polyester braid |
Torsion | +/- 50 °/m |
Sheathing material | rubber (CR) 5GM5 |
Colour of outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
Oil-resistant | EN 60811-2-1 |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | -40 - +80 °C |
Permitted outer cable temperature, moved, °C | -40 - +80 °C |
Bending radius, fixed installation | 4 x Ø |
Bending radius, moving application | 5 x Ø |
Maximum tensile strength at the conductor | 20 N/mm² |
Operating speed | 180 m/min. |
Core identification | colours acc. to VDE 0293 (HD308) |
Nominal cross section, sqmm | 50 mm² |
Conductor resistance | 0.39 Ohm/km |
Ampacity in air (30 °C) | 202 A |
outer diameter min. | 34 mm |
outer diameter max. | 37 mm |
outer diameter approx. | 37.00 mm |
Tensile strength (permanent) | 3000 N |
Copper weight (GER) | 1680 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 2550 kg |
Unit of measurement | metre |
crane cables / hoist cables | yes |
GOST/EAC | yes |
Nominal voltage | 0,6/1 kV |
Sheathing material | rubber |
Cable shape | round |
Halogen-free | no |
Oil-resistant | yes |
Colour | black |
Conductor construction | class 5 = fine stranded |
Insulation | rubber |
These cables are intended for applications where frequent winding and unwinding is necessary during operation, in particular with simultaneous tensile strain and/or torsional stress and/or forced guidance of the cable. Where excessive stress, particularly high dynamic tensile force may be expected, e.g. as a result of high acceleration figures, the permissible stress limits have to be determined individually.