3x150+3G70/3 0.6/1 KV YE
Your p/nr.
on request
on request
on request
Customs Tariff Number (code number) | 85444995900000000 |
Standard | VDE 0250 T. 811 (with ref. to) |
Conductor material | tinned copper |
Conductor construction | Class 5 = flexible |
Insulation | rubber (EPR) 3GI3 |
Arrangement of protective conductors | split in the outer interstices |
Material inner sheath | rubber GM1b |
Screen | tinned copper braid |
Torsion | +/- 25 °/m |
Sheathing material | rubber (CR) 5GM5 |
Colour of outer sheath | yellow |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
Oil-resistant | EN 60811-2-1 |
Ozone-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -40 - +80 °C |
Permitted outer cable temperature, moved, °C | -25 - +80 °C |
Bending radius, fixed installation | 6 x Ø |
Bending radius, moving application | 10 x Ø |
Maximum tensile strength at the conductor | 15 N/mm² |
Core identification | green-yellow + numbers |
Nominal cross section, sqmm | 150 mm² |
Conductor resistance | 0.132 Ohm/km |
outer diameter approx. | 59.70 mm |
Copper weight (GER) | 5502 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 7150 kg |
Unit of measurement | metre |
crane cables / hoist cables | yes |
Nominal voltage | 0,6/1 kV |
Sheathing material | rubber |
Cable shape | round |
Halogen-free | no |
Oil-resistant | yes |
Colour | yellow |
Conductor construction | class 5 = fine stranded |
Insulation | rubber |
Screened rubber cable for EMC-compatible connection of frequency converters in mining, tunneling, as well as in the industrial and construction sectors. In dry and damp rooms as well as outdoors. The cable is flame-retardant and oil-resistant. For applications with special EMC requirements.
All images shown here are for illustrations and product reference purposes only.