KF TBM H (N)TSCGECWHXOEU 3X50+3X25/3E+ 6/10KV RD
Your p/nr.
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
Customs Tariff Number (code number) | 85446010900000000 |
Standard | DIN VDE 0250-813 (with ref. to) |
Conductor material | tinned copper |
Conductor construction | Class 5 = flexible |
Insulation | rubber 3GI3 |
Electrical field control | inner and outer semiconducting rubber layer |
Pilot conductor | tinned copper conductors, rubber 3GI3, with semi-conductive layer, splitted into three parts in the outer interstices |
Arrangement of protective conductors | mixed braid of tinned copper wires and textile fibers over each core |
Material inner sheath | rubber GM1b |
Monitoring core | Copper wire over the inner sheath |
Torsion | +/- 25 °/m |
Sheathing material | special EVA based halogen free rubber compound |
Colour of outer sheath | red |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
Halogen-free | DIN EN 50267/IEC 60754 |
UV-resistant | yes |
Oil-resistant | EN 60811-404 |
Ozone-resistant | yes |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -40 - +80 °C |
Permitted outer cable temperature, moved, °C | -20 - +60 °C |
Min. distance with S-type diretional changes | 20 x Ø |
Operating speed | 30 m/min. |
Number of cores | 3 |
Nominal cross section, sqmm | 50 mm² |
outer diameter approx. | 55.80 mm |
Copper weight (GER) | 1893 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 4140 kg |
Unit of measurement | metre |
crane cables / hoist cables | yes |
GOST/EAC | yes |
Nominal voltage | 6/10 kV |
Sheathing material | rubber |
Cable shape | round |
Halogen-free | yes |
Oil-resistant | yes |
Colour | red |
Conductor construction | class 5 = fine stranded |
Insulation | rubber |
Flexible cable suitable for reeling drum of tunnel boring machines (TBM) and generally for tunnel application. Other applications have to be agreed with Faber Kabel, otherwise warranty may get lost.
Bending radius: acc. to DIN VDE 0298-3
All images shown here are for illustrations and product reference purposes only.