3x95 + 1x50 + 1X(4x2.5 St)C + 1x(6G62.5 LWL) 6/10 kV RD
Your p/nr.
on request
on request
on request
Customs Tariff Number (code number) | 85446010900000000 |
Conductor material | copper, bare |
Conductor construction | Class 5 = flexible |
Insulation | rubber (EPR) 3GI3 |
Electrical field control | inner and outer semiconducting rubber layer |
Material inner sheath | EPR |
Self-supporting element | aramide |
Sheathing material | rubber 5GM5 |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
Oil-resistant | EN 60811-404 |
Ozone-resistant | yes |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -40 - +80 °C |
Permitted outer cable temperature, moved, °C | -25 - +80 °C |
Bending radius, moving application | 10 x Ø |
Maximum tensile strength at the conductor | 25 N/mm² |
Nominal cross section, sqmm | 95 mm² |
Conductor resistance | 0.206 Ohm/km |
Ampacity in air (30 °C) | 301 A |
Short-circuit current (1 s) | 13.59 kA |
outer diameter approx. | 69.00 mm |
Tensile strength (permanent) | 5700 N |
Tensile strength (dynamic) | 7125 N |
Copper weight (GER) | 3478 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 7500 kg |
Unit of measurement | metre |
Nominal voltage | 6/10 kV |
Sheathing material | rubber |
Cable shape | round |
Halogen-free | no |
Oil-resistant | yes |
Colour | red |
Conductor construction | class 5 = fine stranded |
Insulation | rubber |
The cables are suitable for use high voltage shore connection systems (HVCS), on board the ship and on shore, to supply the ship with electrical power from shore, using control cores and fiber optics to adapt different type of vessels. The cables can be manufactured to order or project-specific with E9/125, 50/125 or 62.5/125 fibres.