min. installation temperature -25 °C installation in free air without UV-protection (cable UV-resistant) cable to a large extent oil resistant flame retardant acc. IEC 60332-1-2 max. permitted temperature at conductor 90 °C cable for use in water
p/nr.Part nameAvailabilityPackagingEUR netto pre-metal per 1.000 m.
0529433x70 + 1x35 + 1X(4x2.5 St + 2x3G62.5 LWL) 6/10 kV RD
on request
Aufmachung

Log in to see prices

New here? Register now
Preis
054606PTL(SC)3X70+1X35+2X(4X2.5ST+2X3G50 FO) RD 10KV
on request
AufmachungPreis
0529703x70 + 1x35 + 2X(4x2.5 St + 2x3G62.5 LWL) 6/10 kV RD
on request
AufmachungPreis
0529283x95 + 1x50 + 1X(4x2.5 St)C + 1x(6G62.5 LWL) 6/10 kV RD
on request
AufmachungPreis
054522PTL(SC) 3X120+70+1X(7X2.5ST)C+12E9 10KV RD
on request
AufmachungPreis
054623PTL(SC)3X185+1X95+1X(5X2.5ST+4X3G62.5LWL)C RD 10KV
on request
AufmachungPreis
0520913x185+1x95+1x(5x2.5ST+4x3E9LWL)C 6/10 kV RD
on request
AufmachungPreis
0529713x185 + 1x95 + 1x(7x2.5ST) + 1x(12G62.5LWL) 6/10 kV RD
in stock
AufmachungPreis
Customs Tariff Number (code number) 85446010900000000
Conductor material copper, bare
Conductor construction Class 5 = flexible
Insulation rubber (EPR) 3GI3
Electrical field control inner and outer semiconducting rubber layer
Material inner sheath EPR
Self-supporting element aramide
Sheathing material rubber 5GM5
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes
Oil-resistant EN 60811-404
Ozone-resistant yes
Max. temperature at conductor, °C 90 °C
Max. short circuit temperature at conductor, °C 250 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -25 - +80 °C
Bending radius, moving application 10 x Ø
Maximum tensile strength at the conductor 25 N/mm²
metal base Cu 150 EUR/100 kg
Unit of measurement metre

The cables are suitable for use high voltage shore connection systems (HVCS), on board the ship and on shore, to supply the ship with electrical power from shore, using control cores and fiber optics to adapt different type of vessels. The cables can be manufactured to order or project-specific with E9/125, 50/125 or 62.5/125 fibres.

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metal regarding the daily market price.

Contact
Cable calculator