cable to a large extent oil resistant max. permitted temperature at conductor 90 °C min. installation temperature -25 °C cable for reeling application monospiral reeling installation in free air without UV-protection (cable UV-resistant) cable for use in water
0549890400500
drum 500 m
Invalid input!
MOQ

MOQ: 0

Delivery time: approx.

Price
Price
Price
0549890401000
drum 1000 m
Invalid input!
MOQ

MOQ: 0

Delivery time: approx.

Price
Price
Price
0549890400000
cut length
Invalid input!
MOQ

MOQ: 0

Delivery time: approx.

Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85446010900
Standard DIN VDE 0250-813 (with ref. to)
Conductor material copper, bare
Conductor construction Class 5 = fine stranded - DIN EN IEC 60228 (VDE 0295)
Insulation rubber (EPR) 3GI3
Electrical field control inner and outer semiconducting rubber layer
Arrangement of protective conductors split in the outer interstices
Material inner sheath EPR
Torsion protection polyester braid
Torsion +/- 25 °/m
Sheathing material rubber (PCP) 5GM5
Colour of outer sheath red
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes
Oil-resistant DIN EN 60811-404 / VDE 0473-811-404 / IEC 60811-404
Ozone-resistant yes
Water-resistant yes
Max. temperature at conductor, °C 90 °C
Max. short circuit temperature at conductor, °C 250 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -25 - +80 °C
Min. bending radius, fixed installation 6 x Ø
Min. distance with S-type diretional changes 20 x Ø
Bending radius, moving application 10 x Ø
Operating speed monospiral (two ways), m/min. 160 m/min.
Operating speed monospiral (one way), m/min. 200 m/min.
Number of cores 3
Nominal cross section, sqmm 50 mm²
Conductor resistance 0.386 Ohm/km
Ampacity in air (30 °C) 215 A
outer diameter approx. 48.50 mm
Tensile strength (permanent) 3000 N
Tensile strength (dynamic) 3750 N
Copper weight (GER) 1680
metal base Cu 150 EUR/100 kg
net weight per 1000 3640 kg
Unit of measurement metre
Nominal voltage 8,7/15 kV
Sheathing material rubber
Cable shape round
Halogen-free no
Oil-resistant yes
Colour red
Insulation rubber

Medium‑voltage cable assembly with integrated fibre optics (FO).
Suitable for medium mechanical loads, such as reeling operation, deflection in multiple planes, and torsion. Fibre types: made to order / project‑specific: 9/125 µm (SM), 50/125 µm or 62.5/125 µm (MM)

- Min. bending radius: acc. to VDE 0298-3
- Max. Current carrying capacity: acc. to VDE 0298-4 table 15

All images shown here are for illustrations and product reference purposes only.

Contact