flame retardant acc. IEC 60332-1-2 max. permitted temperature at conductor 90 °C cable to a large extent oil resistant min. installation temperature -25 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water
p/nr.Part nameAvailabilityPackagingEUR netto pre-metal per 1.000 m.
0515573X120+3X70/3 3.6/6 kV RD
on request
Aufmachung

Log in to see prices

New here? Register now
Preis
0512643X50+3X50/3 6/10 kV RD
on request
AufmachungPreis
Customs Tariff Number (code number) 85446010900000000
Standard DIN VDE 0250-813 (with ref. to)
Conductor material bare copper strand
Conductor construction Class 5 = flexible
Insulation rubber (EPR) 3GI3
Electrical field control inner and outer semiconducting rubber layer
Arrangement of protective conductors split in the outer interstices
Material inner sheath EPR
Torsion +/- 100 °/m
Sheathing material rubber (CR) 5GM3
Colour of outer sheath red
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes
Oil-resistant EN 60811-404
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -25 - +60 °C
Bending radius, fixed installation 6 x Ø
Bending radius, moving application 15 x Ø
Maximum tensile strength at the conductor 15 N/mm²
Core identification numbers
metal base Cu 150 EUR/100 kg
Unit of measurement metre
crane cables / hoist cables yes

Medium-voltage rubber cable for energy distribution along conveyor systems. Preferable for fixed installation.

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metal regarding the daily market price.

Contact
Cable calculator