flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free cable to a large extent oil resistant max. permitted temperature at conductor 90 °C min. installation temperature -40 °C installation in free air without UV-protection (cable UV-resistant)
0530000400500
drum 500 m
Invalid input!
on request
Price
Price
Price
0530000401000
drum 1000 m
Invalid input!
on request
Price
Price
Price
0530000400000
cut length
Invalid input!
on request
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85446010900000000
Standard UL 1072
Conductor material tinned copper
Conductor construction Class 5 = flexible
Insulation FRNC-compound
Electrical field control inner and outer semiconducting rubber layer
Sheathing material special FRNC-compound
Colour of outer sheath black
Flame-retardant DIN EN 50266-2-4/VDE 0482-266-2-4/IEC 60332-3-24 (cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
UV-resistant yes
Oil-resistant EN 60811-404
Ozone-resistant yes
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -40 - +80 °C
Bending radius, fixed installation 6 x Ø
Bending radius, moving application 10 x Ø
Maximum tensile strength at the conductor 15 N/mm²
Nominal cross section, sqmm 95 mm²
Conductor resistance 0.21 Ohm/km
Ampacity in air (30 °C) 300 A
Short-circuit current (1 s) 13.58 kA
outer diameter approx. 35.00 mm
Copper weight (GER) 1128
metal base Cu 150 EUR/100 kg
net weight per 1000 2000 kg
Unit of measurement metre
crane cables / hoist cables yes
UL/CSA yes
Nominal voltage 15 kV
Sheathing material FRNC-rubber
Cable shape round
Halogen-free yes
Oil-resistant yes
Colour black
Conductor construction class 5 = fine stranded
Insulation FRNC-rubber

Single core cables are used in short lengths, e.g. for the connection of switchgear cubicles and for the connection of mobile transformer substations. When laying and during operation, care should be taken to protect them from excessive mechanical stress