2% Rabatt auf Online-Bestellungen
Details
flame retardant acc. IEC 60332-1-2 cable to a large extent oil resistant max. permitted temperature at conductor 90 °C cable for reeling application monospiral reeling cylindric drum min. installation temperature -30 °C installation in free air without UV-protection (cable UV-resistant)
0526170400500
drum 500 m
Invalid input!
on request
Price
Price
Price
0526170401000
drum 1000 m
Invalid input!
on request
Price
Price
Price
0526170400000
cut length
Invalid input!
on request
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85446010900000000
Standard DIN VDE 0250-813 (with ref. to)
Conductor material tinned copper
Conductor construction Class 5 = flexible
Insulation rubber 3GI3
Electrical field control inner and outer semiconducting rubber layer
Central filler semiconductive compound on Kevlar® element
Core wrapping semiconductive tape
Arrangement of protective conductors arrange in the outer interstice
Material inner sheath rubber Gm1b/5GM5
Torsion protection polyester braid
Torsion +/- 25 °/m
Sheathing material rubber (CR) 5GM5
Colour of outer sheath red
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes
Oil-resistant EN 60811-404
Ozone-resistant yes
Max. temperature at conductor, °C 90 °C
Max. short circuit temperature at conductor, °C 250 °C
Permitted outer cable temperature, fixed, °C -50 - +80 °C
Permitted outer cable temperature, moved, °C -30 - +80 °C
Operating speed 300 m/min.
Number of fibres 12 n
Nominal cross section, sqmm 25 mm²
outer diameter approx. 44.60 mm
Copper weight (GER) 960
metal base Cu 150 EUR/100 kg
Reelable yes
net weight per 1000 2930 kg
Unit of measurement metre
crane cables / hoist cables yes
Nominal voltage 3,6/6 kV
Sheathing material rubber
Cable shape round
Halogen-free no
Oil-resistant yes
Colour red
Conductor construction class 5 = fine stranded
Insulation rubber

Flexible medium voltage reeling cable with fiber optic wires, for high and extreme mechanical stress, e.g. torsional stress, deflection and high reeling speed. Other applications have to be agreed with Faber otherwise warranty may become void. The cables can be manufactured to order or project-specific with E9/125, 50/125 or 62.5/125 fibres.
- Min. bending radius: acc. to VDE 0298-3
- Max. current rating: acc. to VDE 0298-4

All images shown here are for illustrations and product reference purposes only.

Contact
Cable calculator