flame retardant acc. IEC 60332-1-2 cable to a large extent oil resistant max. permitted temperature at conductor 90 °C min. installation temperature -25 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water
p/nr.Part nameAvailabilityPackagingEUR netto pre-metal per 1.000 m.
051383PTL(ST) (N)TSCGEWOEU 3X25 + 3X16/3E 6/10 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

Presentation

Log in to see prices

New here? Register now
Price
051267PTL(ST) (N)TSCGEWOEU 3X35 + 3X16/3E 6/10 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
051331PTL(ST) (N)TSCGEWOEU 3X50 + 3X25/3E 6/10 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
052368PTL(ST) NTSCGEWOEU 3X95 + 3X50/3E 6/10 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
054844PTL(ST) NTSCGEWOEU 3X150+3X70/3E 6/10KV RD
MOQ

MOQ: m

Delivery time: approx. week

PresentationPrice
051400PTL(ST) NTSCGEWOEU 3X185 + 3X95/3E 6/10 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
051332PTL(ST) NTSCGEWOEU 3X25 + 3X16/3E 12/20 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
051477PTL(ST) NTSCGEWOEU 3X35 + 3X16/3E 12/20 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
051816PTL(ST) NTSCGEWOEU 3X50 + 3X25/3E 12/20 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
051637PTL(ST) NTSCGEWOEU 3X95 + 3X50/3E 12/20 kV RD
MOQ

MOQ: 1 km

Delivery time: approx. 34 weeks

PresentationPrice
Customs Tariff Number (code number) 85446010900000000
Standard DIN VDE 0250-813 (with ref. to)
Conductor material tinned copper
Conductor construction Class 5 = flexible
Insulation rubber 3GI3
Electrical field control inner and outer semiconducting rubber layer
Arrangement of protective conductors tinned copper wire spinning on each core
Material inner sheath basic EPR
Torsion +/- 25 °/m
Sheathing material Gummi 5GM3
Colour of outer sheath red
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
Oil-resistant yes
Ozone-resistant yes
Water-resistant yes
For outdoor use yes
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -25 - +60 °C
Bending radius, fixed installation 6 x Ø
Bending radius, moving application 10 x Ø
Maximum tensile strength at the conductor 15 N/mm²
Number of cores 3
metal base Cu 150 EUR/100 kg
Unit of measurement metre
crane cables / hoist cables yes

Power supply cable for use in water, e.g. for connection to dredgers, floating docks, pumps, etc., in applications where high mechanical stresses are to be expected. Also suitable for use in sewage, salt water and brackish water at water depths of up to 500 m.

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metal regarding the daily market price.

Contact