flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free max. permitted temperature at conductor 90 °C installation in free air only with UV-protection (cable not UV-resistant) cable with VDE-certification cable with EAC-approval cable conform to Low Voltage directive
0149300400500
drum 500 m
Invalid input!
MOQ

MOQ: 1 km

Delivery time: approx. 13 weeks

Price
Price
Price
0149300401000
drum 1000 m
Invalid input!
in stock
Price
Price
Price
0149300401300
drum 1300 m
Invalid input!
MOQ

MOQ: 1 km

Delivery time: approx. 13 weeks

Price
Price
Price
0149300400000
cut length
Invalid input!
in stock
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85444995900000000
CPR-classification according to EN 50575 B2ca
Standard VDE 0276-604
Conductor material copper, bare
Conductor construction class 1, from 25 sqmm class 2
Insulation XLPE 2XI1
Sheathing material FRNC-compound HM4
Colour of outer sheath black
Flame-retardant DIN EN 50266-2-4/VDE 0482-266-2-4/IEC 60332-3-24 (cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C -30 - +70 °C
Permitted outer cable temperature, moved, °C -5 - +70 °C
Bending radius, fixed installation, multicore 12 x Ø
Core identification colours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Conductor shape (Faber) SMv
Number of cores 4
Nominal cross section, sqmm 120 mm²
Conductor resistance 0.153 Ohm/km
Insulation wall thickness 1.2 mm
Ampacity in air (30 °C) 359 A
Short-circuit current (1 s) 17.16 kA
Bending radius, fixed installation 576 mm
outer diameter approx. 43.00 mm
Tensile strength (during installation) 24000 N
Copper weight (GER) 4608
metal base Cu 0 EUR/100 kg
net weight per 1000 5300 kg
Unit of measurement metre
VDE yes
GOST/EAC yes
Nominal voltage 0,6/1 kV
Sheathing material FRNC-compound
Cable shape round
Halogen-free yes
Oil-resistant no
Colour black
Conductor construction class 2 = stranded
Insulation XLPE

Low-smoke, zero-halogen, flame-retardant power cable. For fixed indoor installation as well as in concrete, but not for direct burial in ground or application in water.