cable suitable for direct burial max. permitted temperature at conductor 70 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification cable conform to Low Voltage directive
0902140400500
drum 500 m
Invalid input!
MOQ

MOQ: 5 km

Delivery time: approx. 16 weeks

Price
Price
Price
0902140401000
drum 1000 m
Invalid input!
MOQ

MOQ: 5 km

Delivery time: approx. 16 weeks

Price
Price
Price
0902140400000
cut length
Invalid input!
MOQ

MOQ: 5 km

Delivery time: approx. 16 weeks

Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85446090000000000
Standard VDE 0276-603
Conductor material aluminium
Insulation PVC
Sheathing material polyethylene DMP2
Colour of outer sheath black
Flame-retardant none
UV-resistant yes
For outdoor use yes
Max. temperature at conductor, °C 70 °C
Permitted outer cable temperature, fixed, °C 70 °C
Permitted outer cable temperature, moved, °C -20 - +70 °C
Bending radius, fixed installation 12 x Ø
Core identification colours acc. to VDE 0293 (HD308)
Conductor shape (Faber) SE
Number of cores 4
Nominal cross section, sqmm 150 mm²
Conductor resistance 0.206 Ohm/km
Ampacity in air (30 °C) 246 A
Ampacity in ground (20 °C) 275 A
Short-circuit current (1 s) 11.4 kA
outer diameter approx. 44.00 mm
Tensile strength (during installation) 18000 N
Aluminium weight (GER) 1740
metal base Al (ger) 0 EUR/100 kg
net weight per 1000 2635 kg
Unit of measurement metre
VDE yes
Nominal voltage 0,6/1 kV
Direct burial yes
Sheathing material polyethylene
Cable shape round
Halogen-free no
Oil-resistant no
Colour black
Conductor construction class 1 = solid
Insulation PVC

For fixed installation indoors, outdoors, in the ground, in water and in conrete.