• Sprache wechseln DE
    |
    EN
  • Cart
0 0

(N)A2XH-J/-O

(N)A2XH-J/-O
flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free max. permitted temperature at conductor 90 °C installation in free air only with UV-protection (cable not UV-resistant) cable conform to Low Voltage directive

flame retardant acc. IEC 60332-3-24flame retardant acc. IEC 60332-3-24

cable with low smoke IEC 61034cable with low smoke IEC 61034

cable halogen-freecable halogen-free

max. permitted temperature at conductor 90 °Cmax. permitted temperature at conductor 90 °C

installation in free air only with UV-protection (cable not UV-resistant)installation in free air only with UV-protection (cable not UV-resistant)

cable conform to Low Voltage directivecable conform to Low Voltage directive

  • Item list
  • Technical data
  • Application
  • Technical documents
Standard VDE 0276-604 (with ref. to)
Conductor material aluminium
Conductor class class 2 = stranded
Insulation XLPE 2XI1
Sheathing material FRNC-compound HM4
Colour outer sheath black
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density DIN EN 61034/IEC 61034
Halogen-free DIN EN 50267/IEC 60754
For outdoor use yes
Maximum permitted conductor temperature 90 °C
Permitted outer cable temperature, fixed -30 - +70 °C
Permitted outer cable temperature, in motion/during installation -5 - +70 °C
Nominal voltage Uo 600 V
Nominal voltage U 1000 V
Maximum permitted operating voltage in three-phase systems 1.2 kV
Test voltage 4 kV
Conductor shape (Faber) RM , RMv
Number of cores 1
Nominal cross section 150 mm² , 240 mm² , 300 mm² , 35 mm² , 400 mm² , 50 mm² , 500 mm² , 630 mm² , 95 mm²
Ampacity in air (30 °C) 126 A , 149 A , 234 A , 339 A , 472 A , 547 A , 643 A , 754 A , 882 A
Conductor class class 2 = stranded
Outer diameter approx. 24.2 mm , 26.7 mm , 27 mm , 29.9 mm , 31 mm , 33.1 mm , 33.3 mm , 37.5 mm , 40 mm
Aluminium weight (GER) 1160 kg/km , 1247 kg/km , 1450 kg/km , 1827 kg/km , 435 kg/km , 452,4 kg/km , 652,5 kg/km , 696 kg/km , 870 kg/km

Low-smoke, zero-halogen, flame-retardant power cable. For fixed indoor and outdoor installation as well as in concrete, but not for direct burial in the ground or application in water.

p/nr. Part name Availability Packaging EUR netto pre-metal per 1.000
090272 (N)A2XH-O 01X150 RM 0,6/1 kV SW on request
Stock choose
-
090268 (N)A2XH-O 01X240 RM 0,6/1 kV SW on request
Stock choose
-
090202 (N)A2XH-O 01X300 RM 0,6/1 kV SW on request
Stock choose
-
090269 (N)A2XH-O 01X400 RM 0,6/1 kV SW on request
Stock choose
-
090203 (N)A2XH-O 01X500 RM 0,6/1 kV SW on request
Stock choose
-
090299 (N)A2XH-O 01X630 RM 0,6/1 kV SW on request
Stock choose
-
090412 (N)A2XH-J 04X35 RM/16 RM 0,6/1 kV SW on request
Stock choose
-
090413 (N)A2XH-J 04X50 RM/16 RM 0,6/1 kV SW on request
Stock choose
-
090414 (N)A2XH-J 04X95 RM/50 RM 0,6/1 kV SW on request
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-289
Fax +49 681 97 11-289