(N)AYY FR

(N)AYY FR
flame retardant acc. IEC 60332-3-24 cable suitable for direct burial max. permitted temperature at conductor 70 °C min. installation temperature -5 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable conform to Low Voltage directive

flame retardant acc. IEC 60332-3-24flame retardant acc. IEC 60332-3-24

cable suitable for direct burialcable suitable for direct burial

max. permitted temperature at conductor 70 °Cmax. permitted temperature at conductor 70 °C

min. installation temperature -5 °Cmin. installation temperature -5 °C

installation in free air without UV-protection (cable UV-resistant)installation in free air without UV-protection (cable UV-resistant)

cable for use in watercable for use in water

cable conform to Low Voltage directivecable conform to Low Voltage directive

  • Item list
  • Technical data
  • Application
  • Technical documents
Standard VDE 0276-603 (with ref. to)
Conductor material aluminium
Insulation PVC DIV 4
Sheathing material PVC TM2
Colour outer sheath black
Flame-retardant VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
UV-resistant yes
For outdoor use yes
Maximum permitted conductor temperature 70 °C
Permitted outer cable temperature, fixed 70 °C
Permitted outer cable temperature, in motion/during installation -5 - +70 °C
Nominal voltage Uo 600 V
Protective conductor yes
Nominal voltage U 1000 V
Maximum permitted operating voltage in three-phase systems 1.2 kV
Test voltage 4 kV
Core identification colours acc. to VDE 0293 (HD308)
Number of cores 5
Nominal cross section 95 mm²
Conductor resistance 0.32 Ohm/km
Ampacity in air (30 °C) 186 A
Ampacity in ground (20 °C) 215 A
Conductor class class 2 = stranded
Outer diameter approx. 47.5 mm
Aluminium weight (GER) 1378 kg/km

Power cable with improved flame-retardance. For fixed installation indoors, outdoors, in ground and in water.

p/nr. Part name Availability Packaging EUR netto pre-metal per 1.000
090320 (N)AYY-J FR 05X95 RM SW IEC 332-3-24 Stock
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metall regarding the daily market price.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-289
Fax +49 681 97 11-289