FG16OR16 5G16 GY CEI 20-13 IEC 60502-1
Your p/nr.
on request
in stock
in stock
Customs Tariff Number (code number) | 85444995900000000 |
CPR-classification according to EN 50575 | Cca |
Standard | CEI 20-13, IEC 60502-1 |
Conductor material | copper, bare |
Conductor construction | Class 5 = flexible |
Insulation | HEPR |
Sheathing material | PVC |
Colour of outer sheath | grey |
Water-resistant | AD7 |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -15 - +90 °C |
Permitted outer cable temperature, moved, °C | 0 - +90 °C |
Bending radius, fixed installation | 4 x Ø |
Maximum tensile strength at the conductor | 50 N/mm² |
Core identification | grün-gelb, blau, braun, schwarz, grau |
Number of cores | 5 |
Nominal cross section, sqmm | 16 mm² |
Conductor resistance | 1.21 Ohm/km |
Insulation wall thickness | 0.7 mm |
Ampacity in air (30 °C) | 80 A |
Ampacity in ground (20 °C) | 72 A |
Wall thickness of sheath | 1.8 mm |
outer diameter approx. | 24.40 mm |
Copper weight (GER) | 768 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 1119 kg |
Unit of measurement | metre |
Nominal voltage | 0,6/1 kV |
Direct burial | yes |
Sheathing material | PVC |
Cable shape | round |
Colour | grey |
Conductor construction | class 5 = fine stranded |
Insulation | rubber |
Cables for fixed installation indoors, outdoors, in ducts as well as in the ground (acc. to CEI-67).
All images shown here are for illustrations and product reference purposes only.