(N)2XCY 4X240 SM/70 0.6/1 kV BK acc. to VDE 0276
Your p/nr.
on request
on request
Customs Tariff Number (code number) | 85444995900000000 |
Standard | VDE 0276-603 (with reference to) |
Conductor material | copper, bare |
Conductor construction | class 1, from 25 sqmm class 2 |
Insulation | XLPE DIX3 |
Concentric conductor | Cu |
Sheathing material | PVC DMV6 |
Colour of outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -30 - +70 °C |
Permitted outer cable temperature, moved, °C | -5 - +70 °C |
Bending radius, fixed installation | 12 x Ø |
Core identification | colours acc. to VDE 0293 (HD308) |
Conductor shape (Faber) | SMv |
Number of cores | 4 |
Nominal cross section, sqmm | 240 mm² |
Conductor resistance | 0.0754 Ohm/km |
Ampacity in air (30 °C) | 564 A |
Ampacity in ground (20 °C) | 509 A |
outer diameter approx. | 58.00 mm |
Copper weight (GER) | 9996 |
metal base Cu | 0 EUR/100 kg |
net weight per 1000 | 10953 kg |
Unit of measurement | metre |
Nominal voltage | 0,6/1 kV |
Direct burial | yes |
Sheathing material | PVC |
Cable shape | round |
Halogen-free | no |
Oil-resistant | no |
Maximum tensile strength (installation), N | 50 N |
Colour | black |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
For fixed installation indoors, outdoors, in ground and in water.
All images shown here are for illustrations and product reference purposes only.