(N)YYoek-J

Item list
Technical data
Application
Technical documents
Customs Tariff Number (code number) | 85446010000000000 |
Conductor material | copper, bare |
Insulation | PVC YI4 |
Sheathing material | PVC YM3 |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
For outdoor use | yes |
Max. temperature at conductor, °C | 70 °C |
Permitted outer cable temperature, fixed, °C | 70 °C |
Permitted outer cable temperature, moved, °C | -5 - +70 °C |
Conductor shape | round |
Conductor shape (Faber) | RE |
Nominal cross section, sqmm | 1.5 mm² |
Conductor resistance | 12.1 Ohm/km |
Ampacity in air (30 °C) | 19 A |
Ampacity in ground (20 °C) | 27 A |
Short-circuit current (1 s) | 0.17 kA |
Colour of outer sheath | black |
metal base Cu | 0 EUR/100 kg |
Unit of measurement | metre |
For fixed installation indoors and outdoors, also for direct burial in the the ground. Preferably for power supply and control of oil and fuel pumps, dispensing pumps and similar systems. The resistance to oil and fuel is proofed by BAM-test report VI. 34/10389/96 and tests according to VDE 0472 p. 803, test B. (BAM = Federal Institute for Materials Research and Testing)
p/nr. | Part name | Availability | Packaging | EUR netto pre-metal per 1.000 |
011125 | (N)YYOEK-J 03X1.5 BK | in stock | ||
011126 | (N)YYOEK-J 05X1.5 BK | in stock | ||
011127 | (N)YYOEK-J 07X1.5 BK | in stock |
All images shown here are for illustrations and product reference purposes only.
Freight cost extra. Prices plus metal regarding the daily market price.