N2XY-O 1X240 RM 0.6/1 kV VDE 0276 BK
Your p/nr.
MOQ
MOQ: 6 km
Delivery time: approx. 9 weeks
MOQ
MOQ: 6 km
Delivery time: approx. 9 weeks
MOQ
MOQ: 6 km
Delivery time: approx. 9 weeks
Customs Tariff Number (code number) | 85444995900000000 |
CPR-classification according to EN 50575 | Eca |
Standard | VDE 0276-603 |
Conductor material | copper, bare |
Conductor construction | class 1, from 25 sqmm class 2 |
Insulation | XLPE DIX3 |
Sheathing material | PVC DMV6 |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | -35 - +70 °C |
Permitted outer cable temperature, moved, °C | -5 - +70 °C |
Bending radius, fixed installation | 15 x Ø |
Core identification | colours acc. to HD 308; more than 5 cores: numbers |
Conductor shape (Faber) | RMv |
Number of cores | 1 |
Nominal cross section, sqmm | 240 mm² |
Conductor resistance | 0.0754 Ohm/km |
Ampacity in air (30 °C) | 604 A |
Ampacity in ground (20 °C) | 517 A |
outer diameter approx. | 26.00 mm |
Copper weight (GER) | 2304 |
metal base Cu | 0 EUR/100 kg |
net weight per 1000 | 2415 kg |
Unit of measurement | metre |
Nominal voltage | 0,6/1 kV |
Direct burial | yes |
Sheathing material | PVC |
Cable shape | round |
Halogen-free | no |
Oil-resistant | no |
Colour | black |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
For fixed installation indoors, outdoors, in ground and in water.
All images shown here are for illustrations and product reference purposes only.