1X185 RM 6.35/11 kV RD (BS 7835)
Your p/nr.
MOQ
MOQ: 5 km
Delivery time: approx. 16 weeks
MOQ
MOQ: 5 km
Delivery time: approx. 16 weeks
MOQ
MOQ: 5 km
Delivery time: approx. 16 weeks
Customs Tariff Number (code number) | 85446010900000000 |
Conductor material | copper, bare |
Conductor construction | Class 2 = stranded |
Insulation | XLPE |
Electrical field control | inner and outer semiconducting layer (triple extrusion) |
Material inner sheath | halogen-free |
Screen | copper wire or tape on each core |
Armour | steel- or aluminium-wires |
Sheathing material | FRNC-compound HM1 |
Colour of outer sheath | red |
Flame-retardant | VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C) |
Smoke density | DIN EN 61034/IEC 61034 |
Halogen-free | DIN EN 50267/IEC 60754 |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, moved, °C | 0 - 40 °C |
Bending radius, fixed installation | 12 x Ø |
Conductor shape (Faber) | RMv |
Number of cores | 1 |
Nominal cross section, sqmm | 185 mm² |
Conductor resistance | 0.0991 Ohm/km |
outer diameter approx. | 38.30 mm |
Copper weight (GER) | 2059 |
metal base Cu | 0 EUR/100 kg |
net weight per 1000 | 2980 kg |
Unit of measurement | metre |
Nominal voltage | 6,35/11 kV |
Direct burial | yes |
Sheathing material | FRNC-compound |
Cable shape | round |
Halogen-free | yes |
Oil-resistant | no |
Colour | red |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
The cables are power cables for power networks, underground, outdoors and in cable ducting, in particular for installation where fi re, smoke emission and toxic fumes create a potential threat.