2% Rabatt auf Online-Bestellungen
Details
installation in free air without UV-protection (cable UV-resistant) max. permitted temperature at conductor 90 °C min. installation temperature -20 °C cable for use in water cable suitable for direct burial
p/nr.Part nameAvailabilityPackagingEUR netto pre-metal per 1.000 m.
015509(N)A2XS(F)2Y 3X1X185/25 6/10kV RD
on request
Aufmachung

Log in to see prices

New here? Register now
Preis
Customs Tariff Number (code number) 85446090000000000
Standard VDE 0276-620 (with ref. to)
Conductor material aluminium
Conductor construction Class 2 = stranded
Insulation XLPE DIX8
Electrical field control inner and outer semiconducting layer (triple extrusion)
Screen Copper wires + counter helix
Sheathing material polyethylene DMP2
Longitudinally watertight yes
Colour of outer sheath red
Flame-retardant none
UV-resistant yes
For outdoor use yes
Max. temperature at conductor, °C 90 °C
Permitted outer cable temperature, fixed, °C 70 °C
Permitted outer cable temperature, moved, °C -20 - +70 °C
Bending radius, fixed installation 15 x Ø
Conductor shape (Faber) RMv
Number of cores 3
diameter conductor 16.8 mm
Nominal cross section, sqmm 185 mm²
Conductor resistance 0.164 Ohm/km
Insulation wall thickness 3.4 mm
Ampacity in air (30 °C) 418 A
Ampacity in ground (20 °C) 357 A
Short-circuit current (1 s) 17.4 kA
Wall thickness of sheath 2.1 mm
Bending radius, fixed installation 1055 mm
outer diameter approx. 70.30 mm
Tensile strength (during installation) 16650 N
Aluminium weight (GER) 1610
metal base Al (ger) 0 EUR/100 kg
Copper weight (GER) 848
metal base Cu 0 EUR/100 kg
net weight per 1000 3720 kg
Unit of measurement metre

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation. This cable is also suitable for unfavourable operating conditions, specifically where there is a need to avoid water penetration lengthwise following mechanical damage.

All images shown here are for illustrations and product reference purposes only.

Freight cost extra. Prices plus metal regarding the daily market price.

Contact