N2XS2Y 1X500/35 18/30 kV BK
Your p/nr.
MOQ
MOQ: 5 km
Delivery time: approx. 25 weeks
Customs Tariff Number (code number) | 85446010900000000 |
Standard | VDE 0276-620 |
Conductor material | copper, bare |
Conductor construction | Class 2 = stranded |
Insulation | XLPE DIX8 |
Electrical field control | inner and outer semiconducting layer (triple extrusion) |
Screen | Copper wires + counter helix |
Sheathing material | polyethylene DMP2 |
Colour of outer sheath | black |
Flame-retardant | none |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | 70 °C |
Permitted outer cable temperature, moved, °C | -20 - +70 °C |
Bending radius, fixed installation | 15 x Ø |
Conductor shape | round |
Conductor shape (Faber) | RMv |
Core diameter | 45.6 mm |
Number of cores | 1 |
diameter conductor | 27.6 mm |
Nominal cross section, sqmm | 500 mm² |
Conductor resistance | 0.0366 Ohm/km |
Insulation wall thickness | 8 mm |
Ampacity in air (30 °C) | 953 A |
Ampacity in ground (20 °C) | 765 A |
Short-circuit current (1 s) | 71.5 kA |
Wall thickness of sheath | 2.1 mm |
Bending radius, fixed installation | 795 mm |
outer diameter approx. | 53.00 mm |
Colour of outer sheath | black |
Tensile strength (during installation) | 25000 N |
Copper weight (GER) | 5194 |
metal base Cu | 0 EUR/100 kg |
net weight per 1000 | 6200 kg |
Unit of measurement | metre |
VDE | yes |
GOST/EAC | yes |
Nominal voltage | 18/30 kV |
Direct burial | yes |
Sheathing material | polyethylene |
Cable shape | round |
Oil-resistant | no |
Colour | black |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. It should be noted during installation in cable ducts and interior spaces that the PE-sheath is zero-halogen, yet not flame-retardant as defined under DIN VDE 0482-332-1. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation.
All images shown here are for illustrations and product reference purposes only.