• Sprache wechseln DE
    |
    EN
  • Cart
0 0

NA2XS(F)2Y 01X500/35 18/30 kV SW

Art.-Nr. 011542

NA2XS(F)2Y 01X500/35 18/30 kV SW
cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification

cable suitable for direct burialcable suitable for direct burial

max. permitted temperature at conductor 90 °Cmax. permitted temperature at conductor 90 °C

min. installation temperature -20 °Cmin. installation temperature -20 °C

installation in free air without UV-protection (cable UV-resistant)installation in free air without UV-protection (cable UV-resistant)

cable for use in watercable for use in water

cable with VDE-certificationcable with VDE-certification

  • Item list
  • Technical data
  • Application
  • Technical documents
StandardVDE 0276-620
Conductor materialaluminium
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialpolyethylene DMP2
Longitudinally watertightyes
Colour outer sheathblack
Flame-retardantno
UV-resistantyes
For outdoor useyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-20 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo18000 V
Nominal voltage U30000 V
Maximum permitted operating voltage in three-phase systems36 kV
Test voltage63 kV
Conductor shape (Faber)RMv
Number of cores1
Conductor diameter27.6 mm
Nominal cross section500 mm²
Conductor resistance0.0605 Ohm/km
Insulation wall thickness8 mm
Ampacity in air (30 °C)764 A
Ampacity in ground (20 °C)616 A
Short-circuit current (1 s)47 kA
Wall thickness of sheath2.5 mm
Bending radius, fixed installation795 mm
Conductor classclass 2 = stranded
Outer diameter approx.53 mm
Colour of outer sheathblack
Tensile strength (during installation)15000 N
Aluminium weight (GER)1450 kg/km
Copper weight (GER)394 kg/km
VDEyes
Nominal voltage18/30 kV
Direct burialyes
Cable shaperound
colourblack

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation. This cable is also suitable for unfavourable operating conditions, specifically where there is a need to avoid water penetration lengthwise following mechanical damage.

p/nr. Part name Availability Packaging EUR netto pre-metal per 1.000
011542 NA2XS(F)2Y 01X500/35 18/30 kV SW Stock
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-289
Fax +49 681 97 11-289