NA2XS2Y 01X630/35 18/30 kV SW

Art.-Nr. 013116

NA2XS2Y 01X630/35 18/30 kV SW
cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification

cable suitable for direct burialcable suitable for direct burial

max. permitted temperature at conductor 90 °Cmax. permitted temperature at conductor 90 °C

min. installation temperature -20 °Cmin. installation temperature -20 °C

installation in free air without UV-protection (cable UV-resistant)installation in free air without UV-protection (cable UV-resistant)

cable for use in watercable for use in water

cable with VDE-certificationcable with VDE-certification

  • Item list
  • Technical data
  • Application
  • Technical documents
StandardVDE 0276-620
Conductor materialaluminium
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialpolyethylene DMP2
Colour outer sheathblack
Flame-retardantno
UV-resistantyes
For outdoor useyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-20 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo18000 V
Nominal voltage U30000 V
Maximum permitted operating voltage in three-phase systems36 kV
Test voltage63 kV
Conductor shape (Faber)RMv
Number of cores1
Conductor diameter32.5 mm
Nominal cross section630 mm²
Conductor resistance0.0469 Ohm/km
Insulation wall thickness8 mm
Ampacity in air (30 °C)890 A
Ampacity in ground (20 °C)675 A
Short-circuit current (1 s)59.2 kA
Wall thickness of sheath2.5 mm
Bending radius, fixed installation930 mm
Conductor classclass 2 = stranded
Outer diameter approx.62 mm
Tensile strength (during installation)18900 N
Aluminium weight (GER)1827 kg/km
Copper weight (GER)394 kg/km
VDEyes
Nominal voltage18/30 kV
Direct burialyes
Cable shaperound
colourblack

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. It should be noted during installation in cable ducts and interior spaces that the PE-sheath is zero-halogen, yet not flame-retardant as defined under DIN VDE 0482-332-1. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation.

p/nr. Part name Availability Packaging EUR netto pre-metal per 1.000
013116 NA2XS2Y 01X630/35 18/30 kV SW on request
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-289
Fax +49 681 97 11-289