Customs Tariff Number (code number) 76149000000000000
Standard DIN 48201 T5 (with ref. to)
Conductor construction 53 x 4,36
Conductor material aluminium
Max. temperature at conductor, °C 80 °C
Conductor resistance 0.0357 Ohm/km
Ampacity in air (30 °C) 1329 A
outer diameter approx. 39.20 mm
Aluminium weight (GER) 2510
metal base Al (ger) 0 EUR/100 kg
net weight per 1000 2510 kg
Unit of measurement metre
Colour blank

Bare overhead line made of the material E-AL F7
The current carrying capacity is based on: up to 60 Hz at maximum permissible cable temperature: 80 °C, ambient temperature: 35 °C, solar radiation: 900 W/m², wind speed: from 0.6 m/s.

All images shown here are for illustrations and product reference purposes only.