3X50 + 3X25/3E 6/10 kV RD
Your p/nr.
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
MOQ
MOQ: 1 km
Delivery time: approx. 34 weeks
Customs Tariff Number (code number) | 85446010900000000 |
Standard | DIN VDE 0250-813 (with ref. to) |
Conductor material | tinned copper |
Conductor construction | Class 5 = flexible |
Insulation | rubber (EPR) 3GI3 |
Electrical field control | inner and outer semiconducting rubber layer |
Arrangement of protective conductors | tinned copper wire braid over each phase |
Material inner sheath | rubber GM1b |
Sheathing material | rubber (CR) 5GM5 |
Colour of outer sheath | red |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
Oil-resistant | EN 60811-404 |
Ozone-resistant | yes |
Max. temperature at conductor, °C | 90 °C |
Max. short circuit temperature at conductor, °C | 250 °C |
Permitted outer cable temperature, fixed, °C | -40 - +90 °C |
Permitted outer cable temperature, moved, °C | -25 - +60 °C |
Bending radius, fixed installation | 6 x Ø |
Bending radius, moving application | 15 x Ø |
Maximum tensile strength at the conductor | 15 N/mm² |
Number of cores | 3 |
Nominal cross section, sqmm | 50 mm² |
Conductor resistance | 0.393 Ohm/km |
outer diameter approx. | 51.90 mm |
Copper weight (GER) | 1758 |
metal base Cu | 150 EUR/100 kg |
net weight per 1000 | 3635 kg |
Unit of measurement | metre |
crane cables / hoist cables | yes |
GOST/EAC | yes |
Nominal voltage | 6/10 kV |
Sheathing material | rubber |
Cable shape | round |
Oil-resistant | yes |
Colour | red |
Conductor construction | class 5 = fine stranded |