Your search delivered no result.

N2XH-J with improved fire performance

N2XH-J is a halogen-free and flame-retardant low voltage cable for fixed installation with improved fire performance. As a halogen-free power cable, N2XH is used when public buildings or industrial facilities need an increased level of fire safety. As the cable is halogen-free, it helps to avoid potential consequential damage from a fire.

Design of the N2XH-J cable

The VDE-tested low voltage cable N2XH has a one- or multi-core copper conductor, a wire insulation made from cross-linked polyethylene, a plastic filling and a halogen-free outer sheath. The -J version of the power cable has a protective conductor in the colours green and yellow; this conductor is not present in the -O version of the cable.

Key features of N2XH-J cables

The key feature of N2XH, apart from being halogen-free, is its improved fire performance (= bundle test). Low smoke density keeps escape routes open. N2XH-J/-O cables are suitable for installation indoors, in air and in concrete. Direct burial in the ground or in water is not permitted.

N2XH-J cable: Overview of specifications

Here you have key N2XH technical parameters at a glance:

Conductor material: Cu, bare
Conductor class: Class 1, 25+ mm2 class 2
Core insulation: VPE 2XI1
Sheath material: halogen-free polymer HM4
Sheath colour: black
Flame-retardant: DIN EN 50266-2-4/VDE 0482-266-2-4/IEC 60332-3-24 (cat. C)
Smoke density: DIN EN 61034/IEC 61034
Halogen-free: DIN EN 50267/IEC 60754
Temperature ranges:
Maximum, permissible conductor temperature, °C: 90°C
Permissible outer cable temperature, fixed installation, °C: -30–+70°C
Permissible outer cable temperature, in movement, °C: -5–+70°C
Bending radius, fixed installation: 15 x DA
Nominal voltage Uo: 600V
Nominal voltage U: 1kV
Maximum voltage in 3-phase current systems: 1.2kV
Test voltage: 4kV

Please see the N2HX-J/-O specifications data sheet for more details.

Flame-retardant N2XH power cables in your Faber B2B shop

As your reliable and competent partner for cables and wires, Faber stocks all common N2XH-J and N2XH-O cross-sections. Typical cross-sections are N2XH-J 3x2.5 and N2XH-J 3x1.5. The products are available as 500m and 1000m original drums but also as cut lengths. Please do not hesitate to get in touch should you need help when choosing the right cables or wires. You can contact our experts at any time.

Contact