NA2XY-O 1X120 RM 0.6/1 kV BK
Your p/nr.
on request
on request
on request
Customs Tariff Number (code number) | 85446090000000000 |
CPR-classification according to EN 50575 | Eca |
Standard | VDE 0276-603 |
Conductor material | aluminium |
Insulation | XLPE DIX3 |
Sheathing material | PVC DMV6 |
Colour of outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | 90 °C |
Permitted outer cable temperature, moved, °C | -5 - +70 °C |
Bending radius, fixed installation | 15 x Ø |
Core identification | colours acc. to VDE 0293 (HD308) |
Conductor shape (Faber) | RMv |
Number of cores | 1 |
Nominal cross section, sqmm | 120 mm² |
Conductor resistance | 0.253 Ohm/km |
Insulation wall thickness | 1.2 mm |
Ampacity in air (30 °C) | 295 A |
Ampacity in ground (20 °C) | 272 A |
Short-circuit current (1 s) | 11.2 kA |
Wall thickness of sheath | 1.8 mm |
outer diameter approx. | 20.00 mm |
Tensile strength (during installation) | 3600 N |
Aluminium weight (GER) | 348 |
metal base Al (ger) | 0 EUR/100 kg |
net weight per 1000 | 535 kg |
Unit of measurement | metre |
VDE | yes |
Nominal voltage | 0,6/1 kV |
Direct burial | yes |
Sheathing material | PVC |
Cable shape | round |
Halogen-free | no |
Oil-resistant | no |
Colour | black |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
For fixed installation indoors, outdoors, in the ground, in water and in conrete.
All images shown here are for illustrations and product reference purposes only.