2% Rabatt auf Online-Bestellungen
Details
flame retardant acc. IEC 60332-1-2 cable suitable for direct burial cable with rodent protection (optical fibre) max. permitted temperature at conductor 70 °C min. installation temperature -5 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable conform to Low Voltage directive
0117730400500
drum 500 m
Invalid input!
on request
Price
Price
Price
0117730401000
drum 1000 m
Invalid input!
on request
Price
Price
Price
0117730400000
cut length
Invalid input!
on request
Price
Price
Price

Log in to see prices

New here? Register now
0
Customs Tariff Number (code number) 85444995900000000
Standard VDE 0271
Conductor material copper, bare
Conductor construction class 1, from 25 sqmm class 2
Insulation PVC YI4
Material inner sheath PVC
Armour flat steel wire, galvanized
Sheathing material PVC YM3
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes
For outdoor use yes
Max. temperature at conductor, °C 70 °C
Permitted outer cable temperature, fixed, °C -5 - +70 °C
Bending radius, fixed installation 15 x Ø
Core identification colours acc. to VDE 0293 (HD308)
Conductor shape sector-shaped
Conductor shape (Faber) SMv
Number of cores 3
Nominal cross section, sqmm 70 mm²
Conductor resistance 0.268 Ohm/km
Ampacity in air (30 °C) 199 A
Ampacity in ground (20 °C) 232 A
Short-circuit current (1 s) 8.05 kA
Specific inductivity 0.238 mH/km
outer diameter approx. 35.00 mm
Colour of outer sheath black
Tensile strength (during installation) 10500 N
Copper weight (GER) 2352
metal base Cu 0 EUR/100 kg
net weight per 1000 4028 kg
Unit of measurement metre
Nominal voltage 0,6/1 kV
Direct burial yes
Sheathing material PVC
Cable shape round
Halogen-free no
Oil-resistant no
Colour black
Conductor construction class 2 = stranded
Insulation PVC

As distribution cable for industrial plants and switching boxes. For fixed installation indoors, direct burial in the ground, in water as well as in concrete and for heavy duty mechanical load.

All images shown here are for illustrations and product reference purposes only.

Contact
Cable calculator