NA2XSY 01X70/16 12/20 kV RD

Art.-Nr. 011406

NA2XSY 01X70/16 12/20 kV RD
flame retardant acc. IEC 60332-1-2 cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -5 °C installation in free air only with UV-protection (cable not UV-resistant) cable for use in water cable with VDE-certification

flame retardant acc. IEC 60332-1-2flame retardant acc. IEC 60332-1-2

cable suitable for direct burialcable suitable for direct burial

max. permitted temperature at conductor 90 °Cmax. permitted temperature at conductor 90 °C

min. installation temperature -5 °Cmin. installation temperature -5 °C

installation in free air only with UV-protection (cable not UV-resistant)installation in free air only with UV-protection (cable not UV-resistant)

cable for use in watercable for use in water

cable with VDE-certificationcable with VDE-certification

  • Item list
  • Technical data
  • Application
  • Technical documents
Customs Tariff Number (code number)85446090000000000
StandardVDE 0276-620
Conductor materialaluminium
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialPVC DMV6
Colour outer sheathred
Flame-retardantVDE 0482-332-1-2/IEC 60332-1-2
For outdoor useyes
Maximum permitted conductor temperature, °C90 °C
Permitted outer cable temperature, fixed, °C70 °C
Permitted outer cable temperature, in motion/during installation, °C-5 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo12000 V
Nominal voltage U20000 V
Conductor shape (Faber)RMv
Number of cores1
Conductor diameter10.2 mm
Nominal cross section, sqmm70 mm²
Conductor resistance0.443 Ohm/km
Insulation wall thickness5.5 mm
Ampacity in air (30 °C)231 A
Ampacity in ground (20 °C)210 A
Short-circuit current (1 s)6.58 kA
Wall thickness of sheath2.1 mm
Bending radius, fixed installation465 mm
Outer diameter approx.31 mm
Colour of outer sheathred
Tensile strength (during installation)2100 N
Aluminium weight (GER)203 kg/km
Copper weight (GER)182 kg/km
net weight, ca. kg per 1000 m or pcs.1100 kg
VDEyes
Nominal voltage12/20 kV
Direct burialyes
Cable shaperound
Sheathing materialPVC
Halogen-freeno
Oil-resistantno
colourred
Conductor classclass 2 = stranded
InsulationXLPE

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. According to VDE 0276-603 cables must be protected from sunlight.

p/nr. Part name Availability Packaging EN: EUR netto pre-metal per 1.000
011406 NA2XSY 01X70/16 12/20 kV RD on request
Stock choose
-

All images shown here are for illustrations and product reference purposes only.

The offered products of this online shop are aimed at entrepreneurs according to §14 BGB, traders, freelancer and public organisations. There is no sale for consumers.

Who we are

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact

 

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Deutschland

Phone +49 681 97 11-289
Fax +49 681 97 11-289