NA2XS(F)2Y 3X1X150/25 12/20 kV BK
Your p/nr.
in stock
Customs Tariff Number (code number) | 85446090000000000 |
Standard | VDE 0276-620 |
Conductor material | aluminium |
Conductor construction | Class 2 = stranded |
Insulation | XLPE DIX8 |
Electrical field control | inner and outer semiconducting layer (triple extrusion) |
Screen | Copper wires + counter helix |
Sheathing material | polyethylene DMP2 |
Longitudinally watertight | yes |
Colour of outer sheath | black |
Flame-retardant | none |
UV-resistant | yes |
For outdoor use | yes |
Max. temperature at conductor, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | 70 °C |
Permitted outer cable temperature, moved, °C | -20 - +70 °C |
Bending radius, fixed installation | 15 x Ø |
Conductor shape (Faber) | RMv |
Core diameter | 28.5 mm |
Number of cores | 3 |
diameter conductor | 15 mm |
Nominal cross section, sqmm | 150 mm² |
Conductor resistance | 0.206 Ohm/km |
Insulation wall thickness | 5.5 mm |
Ampacity in air (30 °C) | 366 A |
Ampacity in ground (20 °C) | 319 A |
Short-circuit current (1 s) | 14.1 kA |
Wall thickness of sheath | 2.1 mm |
Bending radius, fixed installation | 1125 mm |
outer diameter approx. | 75.00 mm |
Colour of outer sheath | black |
Tensile strength (during installation) | 13500 N |
Aluminium weight (GER) | 1305 |
metal base Al (ger) | 0 EUR/100 kg |
Copper weight (GER) | 848 |
metal base Cu | 0 EUR/100 kg |
net weight per 1000 | 3875 kg |
Unit of measurement | metre |
VDE | yes |
GOST/EAC | yes |
Nominal voltage | 12/20 kV |
Direct burial | yes |
Sheathing material | polyethylene |
Cable shape | stranded single cable |
Oil-resistant | no |
Colour | black |
Conductor construction | class 2 = stranded |
Insulation | XLPE |
For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation. This cable is also suitable for unfavourable operating conditions, specifically where there is a need to avoid water penetration lengthwise following mechanical damage.