flame retardant acc. IEC 60332-1-2 max. permitted temperature at conductor 90 °C min. installation temperature -25 °C cable with VDE-certification cable with EAC-approval cable conform to Low Voltage directive
0502450400500
drum 500 m
Invalid input!
in stock
Price
Price
Price
0502450401000
drum 1000 m
Invalid input!
MOQ

MOQ: 3 km

Delivery time: approx. 26 weeks

Price
Price
Price
0502450402000
drum 2000 m
Invalid input!
in stock
Price
Price
Price
0502450402500
drum 2500 m
Invalid input!
MOQ

MOQ: 3 km

Delivery time: approx. 26 weeks

Price
Price
Price
0502450400000
cut length
Invalid input!
in stock
Price
Price
Price

Log in to see prices

New here? Register now
0

Discounted residual lengths

0502450400000
Residual length 38 m
Price   Price
Price
Price   Price

Log in to see prices

New here? Register now

Discounted residual lengths

0502450400000
Residual length 38 m
Price   Price
Price
Price   Price

Log in to see prices

New here? Register now
Customs Tariff Number (code number) 85446010900000000
CPR-classification according to EN 50575 Eca
Standard VDE 0250 T. 602
Conductor material tinned copper
Conductor construction Class 5 = flexible
Insulation rubber (EPR) 3GI3
Sheathing material rubber (CR) 5GM3
Flame-retardant VDE 0482-332-1-2/IEC 60332-1-2
UV-resistant yes, only black version
Oil-resistant yes
Ozone-resistant yes
Max. temperature at conductor, °C 90 °C
Max. short circuit temperature at conductor, °C 200 °C
Permitted outer cable temperature, fixed, °C -40 - +80 °C
Permitted outer cable temperature, moved, °C -25 - +80 °C
Bending radius, fixed installation 6 x Ø
Bending radius, moving application 10 x Ø
Number of cores 1
diameter conductor 21.0 mm
Nominal cross section, sqmm 185 mm²
Conductor resistance 0.108 Ohm/km
Ampacity in air (30 °C) 644 A
Short-circuit current (1 s) 22.6 kA
outer diameter approx. 26.00 mm
Colour of outer sheath black
Combustion heat (fire load) 2.6 kWh/m
Tensile strength (during installation) 2775 N
Copper weight (GER) 1776
metal base Cu 150 EUR/100 kg
net weight per 1000 1908 kg
Unit of measurement metre
VDE yes
GOST/EAC yes
Nominal voltage 1,8/3 kV
Sheathing material rubber
Cable shape round
Halogen-free no
Oil-resistant yes
Colour black
Conductor construction class 5 = fine stranded
Insulation rubber

This wire is designed for use in dry rooms, buses and rail-borne vehicles. It is considered to be short circuit-proof and earth leakage-proof when used in switching appliances and distributors of up to 1 kV. It is flame-retardant and resistant to most oils.

All images shown here are for illustrations and product reference purposes only.

The discount on our residual lengths is only valid for orders placed via our Faber B2B webshop.

Contact